UPS to COM Port Connection: Difference between revisions

From OS2World.Com Wiki
Jump to navigation Jump to search
Created page with "Here is a description of the caple needed to connect a Smart-UPS to a COM-Port of a (IBM-)PC. Note: I don't take any responsibility for the correctness of this information. It is provided as is. I provide this information to allow users to manufacture replacement cables, in case the old one gots lost or damaged. I took every effort to insure correctness. Measurements were taken from a cable supplied with an APC Smart-UPS900I which is controlled by APC PowerChute 4.0 fo..."
 
Jugbogdan (talk | contribs)
mNo edit summary
Line 1: Line 1:
Here is a description of the caple needed to connect a Smart-UPS to a COM-Port of a (IBM-)PC.
Here is a description of the cable needed to connect a Smart-UPS to a COM-Port of a (IBM-)PC.


Note: I don't take any responsibility for the correctness of this information.
Note: I don't take any responsibility for the correctness of this information.


It is provided as is. I provide this information to allow users to manufacture replacement cables, in case the old one gots lost or damaged.
It is provided as is. I provide this information to allow users to manufacture replacement cables, in case the old one got lost or damaged.
I took every effort to insure correctness.
I took every effort to insure correctness.
Measurements were taken from a cable supplied with an APC Smart-UPS900I which is controlled by APC PowerChute 4.0 for OS/2.
Measurements were taken from a cable supplied with an APC Smart-UPS900I which is controlled by APC PowerChute 4.0 for OS/2.
It can be assumed, that all Smart-UPS use the same configuration. This may not be true for other UPS lines from APC.
It can be assumed, that all Smart-UPS use the same configuration. This may not be true for other UPS lines from APC.


;UPS-End:
;UPS-End:Male-DB-9 connector, pins being called here U1..U9
Male-DB-9 connector , pins being called here U1..U9
;COM-End:Female-DB-9 connector, pins being called here C1..C9
 
# Connect C1-C4 (shortcut between CD and DTR)
;COM-End:
Female-DB-9 connector , pins being called here C1..C9
 
# Connect C1-C4 (short cut between CD and DTR)
# Connect C2-U2 (data from UPS into RXD)
# Connect C2-U2 (data from UPS into RXD)
# Connect C3-U1 (data from TXD into UPS)
# Connect C3-U1 (data from TXD into UPS)
Line 20: Line 16:
No other connections (resistance less than 10 kOhm) have been found.
No other connections (resistance less than 10 kOhm) have been found.


Connect means : no substantial resistance ( less than 5 Ohm ).
Connect means : no substantial resistance (less than 5 Ohm).


;Remarks:
;Remarks:
Apparently APC went great lengths avoiding any standards to make money with their cables. Avoidance of standards in general brings only problems, increases cost to the end user and may cause hardware damage. The Smart-UPS is really great, the attitude of APC when developing that cable layout not.


Apparently APC went great lengths avoiding any standards to make money with their cables. Avoidance of standards in general brings only problems, increases cost to the end user and may cause hardware damage. The Smart-UPS is really great , the attitude of APC when developing that cable layout not.
The UPS sends data at 2400 bps, 8N1 in regular intervals. The cable does not permit any hardware handshaking (which is bad, because it decreases performance of any software sitting at the other end)
 
The UPS sends data at 2400 bps , 8N1 in regular intervalls. The cable does not permit any hardware handshaking (which is bad, because it decreases performance of any software sitting at the other end)

Revision as of 05:24, 21 November 2023

Here is a description of the cable needed to connect a Smart-UPS to a COM-Port of a (IBM-)PC.

Note: I don't take any responsibility for the correctness of this information.

It is provided as is. I provide this information to allow users to manufacture replacement cables, in case the old one got lost or damaged. I took every effort to insure correctness. Measurements were taken from a cable supplied with an APC Smart-UPS900I which is controlled by APC PowerChute 4.0 for OS/2. It can be assumed, that all Smart-UPS use the same configuration. This may not be true for other UPS lines from APC.

UPS-End
Male-DB-9 connector, pins being called here U1..U9
COM-End
Female-DB-9 connector, pins being called here C1..C9
  1. Connect C1-C4 (shortcut between CD and DTR)
  2. Connect C2-U2 (data from UPS into RXD)
  3. Connect C3-U1 (data from TXD into UPS)
  4. Connect C5-U9 (ground)

No other connections (resistance less than 10 kOhm) have been found.

Connect means : no substantial resistance (less than 5 Ohm).

Remarks

Apparently APC went great lengths avoiding any standards to make money with their cables. Avoidance of standards in general brings only problems, increases cost to the end user and may cause hardware damage. The Smart-UPS is really great, the attitude of APC when developing that cable layout not.

The UPS sends data at 2400 bps, 8N1 in regular intervals. The cable does not permit any hardware handshaking (which is bad, because it decreases performance of any software sitting at the other end)